Leave Your Message

TR D1-10-13200-120/240

    Technical Data

    Primary voltage(V)

    13200

    KVA Rating

    10

    No-Load Loss (W)

    60

    Full Load Loss at 85°C (W)

    82

    Total losses a load factor of 80%(W)

    113

    80% load for distribution transformers (Efficiency in %) 85°C

    98.61

    Impedance (85℃)

    2.2~3.14

    Oil Weight(L)

    89

    Total Weight(KG)

    193

    Dimension(mm)
    A

    780

    B

    730

    ΦD

    520

    H

    950

    Winding Material

    AL-AL

    H.V. TAPS

    13860-13530-13200-12870-12540V

    L.V.

    240/120 V

    Insulation Class

    HV: 15KV  LV: l.2KV

    Tapping Range

    + /-2*2. 5%

    Lightning Impulse Voltage(H. V.)

    95kV

    Lightning Impulse Voltage(L.V.)

    30kV

    Power Frequency Voltage

    38kV

    POLARIDAD:

    SUSTRACTIVA

    Noise Level (dB)

    50

    Max. Winding Temp.

    65℃

    Max Temp.Rise of Top Oil

    60℃

    Hottest spot

    80℃

    Oil

    Mineral Oil (NON-PCB)

    Cooling Type

    ONAN

    No. of H.V. Bushing

    2 Bushings: Porcelain Insulator

    No of L.V. Bushing

    3 Porcelain insulator, lifting ring bolt

    Kind of Insulation

    Outdoor Type

    Frequency

    60Hz

    No. of Phase

    1

    Working Temperature

    -10°C~ +40°C

    Altitude

    1000M

    Circuit Breaker

    None

    An overload signal light

    None

    HV Lightning Arrester

    None

    Tank Color

    ANSI Z55.1No.70 gray

    Tank Material

    Steel

    Nameplate

    Aluminum Nameplate  0.5mm Thickness

    Core Material

    Silicon steel core directional

    Leave Your Message