Ring Main Unit

Place Of Origin: Jiangxi, China

Branding:ECI

Model Number:Module C/Module F/Module V

Makings:aluminum zinc plated sheet

Color:grey

Rated Voltage: 12KV/24KV/36KV/40.5KV

Rated frequency:50HZ/60HZ

Rated current:630A/1250A

    Electrical characteristics

    1The standard electrical

         characteristics  as  follows.

    2·All specifications meet IEC and GB standards,

         ·Gas tank waterproof level up to lp67.

    • IAC(Internal Arc Classification);A-FL or A-FLR.

    Technica

    Data

     

    Unit

    Module C

    Module F

    Module V

     

     

    Load switch

    Switch-fuse

    combination

    Vacuum switch

    Disconnector

    earthing switch

    Rated Voltage

    kv

    12

    24

    36/40.5

    12

    24

    40.5

    12

    24

    36/40.5

    12

    24

    36/40.5

    Rated frequency

    Hz

    50/60

    50/60

    50/60

    50/60

    50/60

    50/60

    50/60

    50/60

    /

    50/60

    50/60

    1

    Rated current

    A

    630

    630

    630

    /

    /

    /

    630/1250

    630/1250

    63/2500

    630/125

    630/1250

    630/2500

    Rated short-circuit making

    current (peak value)

    kA

    50

    50

    50

    Upto

    fuse

    Upto

    fuse

    Upto

    fuse

    50/63

    50/63

    50/62/0

    50/63/8

    50/63/80

    50/63/80

     

    kA

    20/25

    20/25

    20/25

    Upto

    fuse

    Upto

    fuse

    Upto

    fuse

    20/25

    20/25

    20/25/31.5

    20/25

    20/25

    20/25/31.5

    Short-time impulse voltage

    5

    3/4

    3/4

    3/4

    /

    /

    /

    3/4

    3/4

    3/4

    3/4

    3/4

    3/4

    Rated breaking current

    A

    /

    /

    /

    1750

    1000

    800

    /

    /

    /

    /

    /

    /

    Rated power

    frequency

    withstand voltage

    Phase to phase

    kw/1 min

     

    38/42

     

    50/60

     

    70/95

     

    38/42

     

    50/65

     

    /

     

    38/42

     

    50/65

     

    70/95

     

    38/42

     

    50/65

     

    70/95

    Rated lightning

    impulse withstand

    voltage

    Phase to earth

     

    kv

     

    75

     

    125

     

    170/195

     

    75

     

    125

     

    170/185

     

    75

     

    125

     

    170/185

     

    75

     

    125

     

    170/185

    SF6 pressure in sealed enclosure

    Mpa

    0.04

    0.04

    0.04

    0.04

    0.04

    /

    0.04

    0.04

     

    0.04

    0.04

    0.04

    SF6 annual leakage rate

    96

    0.05

    0.05

    0.05

    0.05

    0.05

    /

    0.05

    0.05

    /

    0.05

    0.05

    0.05